24kV-1600A Vs1 Circuit Breakers for Overcurrent Protection
Overview
1. VS1A series of vacuum circuit breakers are the Second Generation indoor switch equipment, with the rated voltage 7.2kv, 12kv, 17.5kv and 24kv.
2. VS1A series of vacuum circuit breakers adopt the integrated design of simple structure and convenient operation.
3. It is equipped with a perfect mechanical and electrical interlock to enhance its anti-incorrect operation performance.
4. Standards: IEC62271-100, IEC56, GB1984-2003, GB/T11022, DL/T403-2000, etc.
Main Specifications and Technical Parameters
Overview
1. VS1A series of vacuum circuit breakers are the Second Generation indoor switch equipment, with the rated voltage 7.2kv, 12kv, 17.5kv and 24kv.
2. VS1A series of vacuum circuit breakers adopt the integrated design of simple structure and convenient operation.
3. It is equipped with a perfect mechanical and electrical interlock to enhance its anti-incorrect operation performance.
4. Standards: IEC62271-100, IEC56, GB1984-2003, GB/T11022, DL/T403-2000, etc.
Main Specifications and Technical Parameters
Item | unit | Data |
Rated voltage | kV | 24 |
1 min power frequency withstand voltage | kV | 65 |
Lightning impulse withstand voltage | kV | 125 |
Rated frequency | Hz | 50 |
Rated current |
A | 1600 |
Rated short-time withstand current | kA | 20,25,31.5 |
Rated peak withstand current | kA | 50,63,80 |
Rated short-circuit breaking current | kA | 20,25,31.5 |
Rated short-circuit closing current | kA | 50,63,80 |
Rated short-circuit duration | S | 4 |
Contact over-travel | mm | 3.5±0.5 |
Clearance between open contacts | mm | 13±1 |
Average opening speed | m/s | 1.3±0.3 |
Average closing speed | m/s | 0.8±0.2 |
Opening time | ms | 35-60 |
Closing time | ms | 20-45 |
Rated operation sequence | O-0.3s-CO-180s-CO(<40kA)/ O-180s-CO-180s-CO(≥40kA) |
|
Mechanical life | cycles | 10000 |
External Dimension
VS1A-24kv-pole center distance 275mm
VS1A-24kv-pole center distance 210mm
No. | Rated Voltage(kV) | Rated current(A) | Short-circuit breaking current(kA) | h1(mm) | h2(mm) | h(mm) | B(mm) |
1 | 24 | 630 | 20-31.5 | 325 | 310 | 768 | 747 |
2 | 24 | 1250 | 20-31.5 | 325 | 310 | 768 | 747 |
3 | 24 | 1250 | 31.5-40 | 345 | 310 | 768 | 747 |
4 | 24 | 1600 | 20-40 | 345 | 310 | 768 | 747 |
VS1A-24kv-pole center distance 275mm
No. | Rated Voltage(kV) | Rated current(A) | Short-circuit breaking current(kA) | h1(mm) | h2(mm) | h(mm) | B(mm) |
1 | 24 | 630 | 20-31.5 | 325 | 310 | 768 | 747 |
2 | 24 | 1250 | 20-31.5 | 325 | 310 | 768 | 747 |
3 | 24 | 1600 | 20-31.5 | 345 | 310 | 768 | 747 |
4 | 24 | 1600-2500 | 20-31.5 | 345 | 310 | 813 | 737 |
Packaging, Transportation and Storage Precautions
(1) Circuit breaker should be in the state of opening and energy storage spring in a state without energy storage when packing. It should be in the state of opening and energy storage spring in a state without energy storage when packing. And it should be fixed on the bottom of the wooden case, should have waterproof measures and complete package labels.
(2) Circuit breakers can't invert and avoid strong vibration, rain, surface damage, and components lost when transportation.
(3) When loading the circuit breaker, we suggest the following tools: crane, forklift and driving. When lifting the circuit breaker, we should not hook on the body or pole of the circuit breaker, but on the lifting hole which has the lifting mark.
(4) When circuit breaker has a long-term storage, it should be in a state of opening and energy storage spring in a state without energy storage and placed in dry ventilated indoor preventing from moisture, vibration control and harmful gas erosion, and regularly checked whether environment meets the requirements.
(5)When first use products after long-term storage, it need to have a power frequency withstand voltage insulation testing.
(1) Circuit breaker should be in the state of opening and energy storage spring in a state without energy storage when packing. It should be in the state of opening and energy storage spring in a state without energy storage when packing. And it should be fixed on the bottom of the wooden case, should have waterproof measures and complete package labels.
(2) Circuit breakers can't invert and avoid strong vibration, rain, surface damage, and components lost when transportation.
(3) When loading the circuit breaker, we suggest the following tools: crane, forklift and driving. When lifting the circuit breaker, we should not hook on the body or pole of the circuit breaker, but on the lifting hole which has the lifting mark.
(4) When circuit breaker has a long-term storage, it should be in a state of opening and energy storage spring in a state without energy storage and placed in dry ventilated indoor preventing from moisture, vibration control and harmful gas erosion, and regularly checked whether environment meets the requirements.
(5)When first use products after long-term storage, it need to have a power frequency withstand voltage insulation testing.
other products